๐Ÿงฎ iCalc โ€” Get iOS App

Motor Full-Load Current

Calculate the full-load current of an electric motor from its power, voltage, efficiency and power factor, free online.
About this calculator

Three-phase: I = P รท (โˆš3 ยท V ยท ฮท ยท pf). Single-phase: I = P รท (V ยท ฮท ยท pf). Conductors are sized for 125% of the full-load current, and the motor overload relay is typically set at 105โ€“115% of the nameplate current.